| Low Risk
| Low - Moderate Risk |
Moderate - High Risk | High - Risk
|
| Location (all tanks) |
| | |
|
| Position of tank in relation to drinking water well.
| Tank downslope more than 100 feet from well in medium - or fine textured soils (silt loam, loam, clay loams, silty clay) with low per - meability.
| Tank at grade or upslope more than 100 feet from well in medium or fine textured soils (silt loam, loam, clay loams, silty clay) with low per - meability *.
| Tank downslope more than 100 feet from well in coarse textured soil (sands, sandy loam,) with high per - meability.
| Tank at grade or upslope less than 100 feet from well in coarse textured soil (sand, sandy loams) with high per - meability.
|
| Tank Location and local land use (leakage potential).
| Well drained soils. Water table always beneath tank. Above ground tank more than 50 feet from buildings.
| Moderately well drained soils. Only occasionally high water table.
| Located more than 50 feet from buildings. Medium or fine textured soils (silt loams, loam, clay loams, silty clay) saturated seasonally.
| Located less than 50 feet from buildings and in areas with fine textured soils (clay loams, silty clay, clay) often saturated.
|
| Design and Installation Table. (all tanks).
| | | |
|
| Type and age of tank corrosion protection.
| Synthetic tank or tank with cathodic corrosion protection..
| steel tank less than 15 years old, coated with paint or asphalt.
| Coated steel tank 15 or more years old. Bare steel tank less than 15 years old.
| Bare steel tank 15 or more years old.
|
| Spill and tank overfill protection.
| Impermeable catch basin plus automatic shutoff.
| Impermeable catch basin plus overfill alarm.
| Impermeable catch basin or concrete catch pad.
| No protection. |
| Piping. | Piping protected from rust and corrosion by cathodic protection. Piping isolated from tank and sloped back to tank. Check valve at pump (not at tank).
| Piping galvanized but not isolated from tank. Pipe drains back to tank. Check valve at pump.
| Piping galvanized, not isolated or bare. Piping sloped back to tank, but check valve is located at tank (foot valve).
| Piping and tank isolated and of dissimilar materials. Uninsulated pipe bare, cannot drain freely to the tank. All pressure pipe systems
|
| tank installation. |
Installed by state certified installer.
| Installed according to recommenda - tions provided with new tank by seller.
| No information installation.
| Installed without backfill, setback, secondary contain - ment, anchors and other protection, or by untrained individual.
|
| Design and Installation (above ground tanks only).
| | | |
|
| Tank enclosure. | Tank surrounded by 6 foot tall non combustible building or fence with lock. Building well ventilated. Firewall in place if setbacks do not conform to code.
| Tank surrounded by low fence with lock. Firewall in place if setbacks do not conform to code.
| Tank surrounded by los fence. No lock. No firewall.
| No enclosure. |
| Secondary contain - ment. |
Tank placed within concrete of synthetic dike with pad able to hold 125% of tank capacity.
| Tank placed within dike and pad made of low per - meability soils*, able to hold 125% of tank capacity.
| Tank placed on pad. |
No secondary contain - ment. |
| Monitoring (all tanks).
| | | |
|
| Tank integrity testing and leak detection monitoring.
| Regular (monthly) leak monitoring.
| Daily inventory control and annual tank tightness testing.
| Occasional inventory control and annual tank tightness testing.
| No inventory control, testing or monitoring.
|
| Tank closure (under - ground tanks).
| | | |
|
| Unused tank. | Tank removed from ground. Excavation checked for evidence of contamin - ation.
| Tank filled with inert material and excavation checked for evidence of leaking.
| Tank removed or filled with inert material. Excavation not checked for contamin - ation.
| Tank left in ground (illegal after 12 months).
|
| * See glossary. |
| | | |